Building permits are required to protect the health, safety and welfare of residents. Failure to obtain the required permit is a violation of the law. Make sure you determine whether your project is considered Residential or Commercial before proceeding.
Learn more about the Commercial Building Permit Review Process.
Submission Requirements
Commercial building permit applications must be submitted online via Permit Arlington. Expand the bulleted items below to view the requirements for several common commercial projects. Refer to Permit Arlington: Online Submission Guidelines for file upload requirements related to your application.
New Construction
- Construction documents, including a cover sheet with the scope of work and Code Analysis (see bottom of page for an example), architectural, structural, mechanical, electrical and plumbing plans, details and schedules.
- Site plans, grading and landscaping plans.
- A wall check may be required per site plan or use permit conditions. The plan reviewer may also request a wall check at their discretion. Wall checks must be submitted as a revision through the Permit Arlington system..
- Water Quality Impact Assessment Data Sheet
- Submit a garage plan, if applicable.
- Use the Seal Chart and Notes for quick reference in order to determine accordance with §54.1-402 of the Code of Virginia if an architect’s or engineer’s (A/E) seal is required on documents for proposed construction.
Addition to an Existing Building
- Construction documents including architectural, structural, mechanical, electrical and plumbing plans, details and schedules.
- Site plans and landscaping plans.
- A wall check may be required per site plan or use permit conditions. The plan reviewer may also request a wall check at their discretion. Wall checks must be submitted as a revision through the Permit Arlington system.
- Survey plat or grading plan showing setbacks, coverage and parking.
- Water Quality Impact Assessment Data Sheet
- Accessibility Compliance
- Any alterations or additions to existing structures require the applicant to complete the Asbestos Inspection and Awareness Form.
- Submit a garage plan, if applicable.
- Use the Seal Chart and Notes for quick reference in order to determine accordance with §54.1-402 of the Code of Virginia if an architect’s or engineer’s (A/E) seal is required on documents for proposed construction.
Interior Alterations
- Construction documents including architectural, structural, mechanical, electrical and plumbing plans, details and schedules.
- Plans must clearly indicate existing work and work to be modified.
- Survey plat (if work involves structural modifications)
- Accessibility Compliance
- Any alterations or additions to existing structures require the applicant to complete the Asbestos Inspection and Awareness Form.
- Submit a garage plan, if applicable.
- Use the Seal Chart and Notes for quick reference in order to determine accordance with §54.1-402 of the Code of Virginia if an architect’s or engineer’s (A/E) seal is required on documents for proposed construction.
Interior Alterations – Express
- Architectural drawings to include Code Analysis (see bottom of page for an example), scaled and dimensioned floor plans, elevations, sections and details, as appropriate; room/door/window schedules, and partition schedules with fire ratings and test numbers, as appropriate. Provide key plan of floor showing renovation space and egress to the identified floor exits. Indicate new and existing work (clouds are not an acceptable method to indicate new work).
- Electrical drawings to include riser diagram, panel / light schedules and power / light plans. Indicate new and existing work.
- Mechanical drawings to show the location of all existing supply and return registers (if the system and ductwork are existing, indicate as such) and complete duct layout with all main and branch sizes, register sizes and Cubic Feet per Minute (CFM) at each register (if ductwork is new). Provide equipment schedule for new equipment.
- Plumbing drawings to include riser diagrams, schedules and layouts. Indicate new and existing work.
- View a list of all permits and requirements.
- Plans must clearly indicate existing work and work to be modified.
- Accessibility Compliance
- Any alterations or additions to existing structures require the applicant to complete the Asbestos Inspection and Awareness Form.
- Submit a garage plan, if applicable.
- Use the Seal Chart and Notes for quick reference in order to determine accordance with §54.1-402 of the Code of Virginia if an architect’s or engineer’s (A/E) seal is required on documents for proposed construction.
Trailers
Requirements for All Trailers
Additional Requirements for Non-Construction Trailers
Fences and Retaining Walls
Retaining walls that are part of a larger project, such as a new commercial building, can be included within the building permit and should be included in the description of work on the application.
Retaining walls that are not included with the building permit application and submission or are not part of a larger project should be submitted as a Fence or Retaining Wall Permit, it should not be submitted as a building permit.
Signs
Any signage should be submitted as a sign permit. it should not be submitted as a building permit.
Maximum Occupant Load Sign for Assembly Rooms or Space
The capacity of assembly occupancies is established by the Virginia Uniform Statewide Building Code. Seating may also be limited by the Arlington County Zoning Ordinance. As part of the building permit process, the maximum occupant load of assembly rooms and spaces will be reviewed by the Inspection Services Division (ISD) and seating will be reviewed by Zoning during the plan review process. If there are not renovations or a change of use and there is not an existing approved maximum occupant load sign, a building permit must be applied for the maximum occupant load to be reviewed. The following must be provided for each assembly room or space as part of the building permit plan review:
- Complete a Maximum Occupant Load Sign for each assembly occupancy room or space with an occupant load of 50 or more, or any restaurants, cafes, or similar uses with indoor or outdoor seating regardless of occupant load. VCC 1004.9 Restaurants typically only requires one sign, while other occupancies such as an office with multiple conference rooms with an occupant load of 50 or more will require multiple signs.
- When a venue has more than one set-up a separate maximum occupant load sign must be provided for each configuration and each configuration must have the following
- Previous and proposed use of the space or previous type of business must be described
- Provide room numbers or suite number, if applicable
- Square footage (area) including dimensions of the space and all rooms in the space
- Seating layout with the number of seats shown and tabulated.
- All objects and furniture, including tables, booths, shelving, cabinets, bar, etc. Show their size and location
- All doors in the exit serving the space and in the exit path, including exterior doors. Show their size, location, direction of door swing, and hardware
- Restrooms serving the space including the layout of all toilets, urinals and lavatories in each restroom.
- Any other spaces that use the same restrooms and exit pathways.
- Show all exit signs.
- Corridor width along the exit path
- Stair width in the exit path
- State on the plans whether the entire building is protected with fire sprinklers
- Key plan if the space is a suite in larger building
- See an example plan
Sample Code Analysis
This sheet is not intended to represent minimum submission requirements for any plan. Any oversight or misinterpretation of this table does not alleviate compliance with code requirements throughout the review and inspection process.
|
Existing Building |
Proposed Alteration |
Unacceptable |
IBC Use Group |
B |
B |
Bank |
Construction Type |
IIIB |
IIIB |
Wood |
Number of Stories Above Grade |
2 |
2 |
? |
High Rise (Yes/No) |
No |
No |
No |
Covered Mall (Yes/No) |
No |
No |
? |
Fully Sprinklered (Yes/No) |
Yes |
Yes |
? |
Fully Monitored (Yes/No) |
No |
Yes |
? |
Floor Area of Renovation |
5000 |
1200 |
See plans |
Fees
Fee Schedules provide the range of fees charged for each type of application or activity related to land development in Arlington. Fees cover permitting, plan review, enforcement, inspection, service delivery, performance agreements and conditions. There are separate fee schedules for Inspection Services Division (ISD), Zoning and the Department of Environmental Services (DES). Some permits involve fees from more than one schedule.